10
DEVICE EXPLANATION
10.7 File Register (R)
10.7.6 Precautions for using file registers
10 - 82
9
Parameters
10
Device Explanation
11
CPU Module Processing
Time
12
Procedure for Writing
Program to CPU ModuleAppendicesIndex
3) Checking the file register capacity
• Check The file register capacity used for each sequence program.
• Determine if the file register capacity exceeds the number of points used,
on the basis of the total file register capacity set in SD647 in the sequence
program.
[Program example 1]
The file register "range of use" is checked at the beginning of each program.
[Program example 2]
The file register "range of use" is checked after executing the QDRSET instruction.
[Program example 3]
For block switching.
(c) File register file deletion
Choose [Online] [Delete PLC data] on GX Developer to delete the unnecessary
file register file.
Figure 10.77 File register checking program example
SM400
M0
Y0
M0
Transfer command
M0
MOVP K4X20 R0
<
SD647 K4
Designates 4k points
Final file register
range check
Writing to file
register
Alarm processing
SM400
M0
Y0
M0
Transfer command
M0
MOVP K14X20 R0
<
SD647 K4
QDRSET "1:ABCD"
Final file register
range check
File register is changed
to drive 1 ABCD.
Writing to file
register
Alarm processing
SM400
M0
Y0
M0
Block switching command
M0
RSET K1
< SD647 K33
Final file register
range check
Alarm processing
Switching to block 1

Table of Contents

Other manuals for Mitsubishi Q02CPU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q02CPU and is the answer not in the manual?

Mitsubishi Q02CPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ02CPU
CategoryController
LanguageEnglish

Related product manuals