Basic Troubleshooting 1-21
Environmental --
External to
Station
Temp Alarm Minor Yes Yes The station has
exceeded the
temperature limit
that will allow
maximum rated
output power
from the PA
Local Dealer:
Remedy 1: If the “Fan
Alarm” is present, this can
cause the “Temp Alarm” to
be issued as a secondary
alarm. If applicable,
correct the “Fan Alarm”
first, see “Fan Alarm”.
Remedy 2: If Remedy 1
does not solve this issue,
verify that there is not a
problem with the site
temperature itself. The
station will clear the “Temp
Alarm” and allow
maximum rated output
power when the
temperature of the site is
lowered.
Remedy 3: If Remedy 1
and Remedy 2 does not
solve this issue, verify that
the rack and cabinet
installations of the station
are in accordance with the
product planner
instructions.
Remedy 4: If Remedy 1,
Remedy 2 and Remedy 3
does not solve this issue,
replace the PA FRU.
Environmental --
External to
Station
Temp Alarm Minor Yes Yes The station has
exceeded the
temperature limit
that will allow
maximum rated
output power
from the PA
Motorola Repair Depot:
Remedy 1: If the “Fan
Alarm” is present, this can
cause the “Temp Alarm” to
be issued as a secondary
alarm. If applicable,
correct the “Fan Alarm”
first, see “Fan Alarm”.
Remedy 2: If Remedy 1
does not solve this issue,
repair/replace/recalibrate
the PA FRU.
Table 1-7 MTR3000 Alarm Diagnosis Table (Continued)
Sub-system Alarm
Name
Alarm
Class
Diag.
View
Diag.
Repeater
Log
Diagnosis Probable Remedy