Description of the System
SUPREMATouch
121
US
MAO Module (Analog Output)
This module is used when analog outputs (max. 256) are installed in the system. Each MAO mod-
ule has 8 analog signal outputs for 0(4) ... 20 mA current loops. The assignment between the out-
puts and the signal inputs can be configured.
Power Supply, Bus Connections, Connecting Technique
MSP Module (System Power Unit)
0 ... 20 mA output drivers, measurement signal outputs (galvanic isolated from system)
Measurement signal output:
Measuring range over flow:
INHIBIT:
Signal failure:
Fail dependent of Free A/Free B
4 ... 20 mA
22 mA (Values between 20 and 22mA are still valid
measuring values, but out of range)
3.0 mA
3.2 mA
(see chapter 10)
Maximum load: 500 Ohm
Data transmitted from the MDO module via the CAN bus A
The System Failure Relay is activated when a processor error occurs
Euro card with a 96-way connector
MSP Module System Power Unit
(power supply unit, 85 ... 265 VAC/24 VDC)
MIB Module Interconnection Board
(rack, bus circuit board)
MST Module System Terminals
(RS 232, RES, ACK, LOCK, CAN)
MAT Module Analog Terminal Unit
(terminals for sensors on the rack)
MAT TS Module ANALOG TERMINAL UNIT
(terminals for sensors on mounting rail)
MUT Module Universal Terminals
(40-way ribbon cable connection)
Rack power supply unit, 150 VA
Wide range input, 85 ... 265 VAC
Output voltage, 24 VDC