273
US
15.7 SUPREMA Sensor Data Sheet Ex-Fire Detector
Apollo Series 60 with Barrier Z 787
Fig. 186
The cable screen is only connected to the SUPREMA.
*1 Connect according to manufacturer´s specification for Apollo Series 60:
SERIES 60 INTRINSICALLY SAFE SYSTEM DRAWING Z209883. Carry out installation ac-
cording to NFPA 72.
Only the mounting support Order No. 45681-207 specified in the data sheets must be used.
For each detection zone circuit, max. 20 fire detectors are allowed.
*2 End of Line Resistor 2K2 / 0.5 W has to be mounted in the last mounting support of the de-
tection zone circuit or in the portable detector according to the documents specified under *1
*3 Indication of leakage current. In the case of failure, the „OPEN COLLECTOR“ transistor is
conducting to terminal 5
Connection module: MFI (Fire Input Module)
Configuration: External power supply, without Zener barrier.
(Switch position S101: 1 + 2 = OFF, 3 + 4 = ON)
Set potentiometer P101 to left position
Connection
data:
Maximum nominal current 42 mA
Maximum nominal voltage 22 V
Power consumption 1.5 W (including cable length)
Cable type 2-core, 80 % screened
Maximum loop resistance 50 ohms (cable resistance)
Maximum cable length 2000 m (1.5 mm
2
cross section per wire)
Cross section per wire allowed 0.5 ... 2.5 mm
2