MSA AUER
MSA
Installation
SUPREMATouch
159
US
10.4 System Configuration (Hardware)
Slot Assignments
After all the modules have been configured (or after their configuration has been checked), all the
required modules should be inserted into the racks or pushed from behind onto the contacts and
fastened in place mechanically by means of the retainers provided.
For each slot on the front there is a corresponding module connector plug on the rear. To install
modules that are to be inserted from the front (i. e. MCP module, MDA module, MAI module,
MGO module, and MAO module) detach the front plate and flip it down. The following rules should
be observed:
Front:
Slots 1-3:
The first 3 slots are reserved exclusively for the MCP and/or MDC module. In systems without re-
dundancy, slot 2 is the standard slot for the MCP module (Chapter 13).
Slots 4-5:
Slots 4 and 5 are reserved exclusively for the MDA module. In systems without redundancy, the
4th slot must be used for the MDA module (Chapter 13).
Slots 6-13:
Slots 6–13 can be filled with MAI, MAO, MBC or MGO modules, as desired.
Slots 14-15:
Slots 14 and 15 may be filled only with MAO, MBC or MGO modules.
Rear:
Connection site 1:
The first connection site is reserved exclusively for the MST module. The racks are shipped with
the MST module installed as standard equipment, so that only Positions 1–10 are available for
configuration.
Position 1-10:
Positions 1-10 can be filled with either MAT, MUT, MRO, or MBT modules, as desired.
NOTE: The MRO 8 module must be installed in POS 9 only! It is impossible to be use more than
one MRO 8 module in one rack.
Assignment: Front: Rear:
Slot 1 MST Module
Slot 2-5 free
Slot 6-15 Pos 1-10