Redundant Systems
SUPREMA
241
US
13.4 Startup
The data stored in every MCP and MDO module contains information on system configuration,
i.e. the modules used, supply voltages, measuring points and alarm outputs.
Also included is the measuring point parameters (sensor type, calibration etc.) and switching out-
put parameters (switching direction etc.) stored in additional maps in every MCP and MDO mod-
ule.
If the configuration listing does not correspond to the system status, “SYSTEM FAILURE“ will be
issued after startup.
After connecting the modules, the configuration stored in the SUPREMA memory has to be up-
dated according to the system status. For detailed information, see section 10.
Configuration Tool
All configuration has to be done, and all paraterization can be done with the PC operating program
called SUPREMA Manager. Version and Article Number see chapter 8.
Function Check
After configuration and parameter setting of the system, a functional check must be carried out:
Start of System
By switching OFF/ON the system, a new startup is effected. During startup, several internal sys-
tem checks are carried out. A system which is working failure-free will show the following settings
after startup:
Front Panel Display
Displays of the Modules
All CAN-BUS modules have the following LED displays:
*= Rack operation via INT terminals
1. LED SYSTEM POWER ON
2. LED SYSTEM FAIL OFF
3. LED SYSTEM INHIBIT OFF
4. LED SIGNAL 1 AL OFF
5. LED SIGNAL 2 AL OFF
6. LED SIGNAL 3 AL OFF
7. LED SIGNAL 4 AL OFF
8. LED SIGNAL FAIL OFF
9. LED Display Display Listing
LED Function Required
LED 1 GN EXT = ON OFF
LED 2 GN INT = ON ON*
LED 3 GN BAT = ON OFF
LED 4 RT CAN-BUS Failure OFF
LED 5 GN CAN-BUS in Operation ON