11.5 Completing Startup
To check the correctness of all the completed adjustments, it is recommended that all the inputs
be tested with test gas. Verify that the correct alarm is triggered and that the correct relay driver
output is actuated. Keep a record of this test.
Startup is complete after a successful final check of the SUPREMA system and of the completed
installation and calibration procedures. Now the external alarm and warning systems can be con-
nected.
WARNING
To guarantee the unambiguity of catalytic combustion sensor operation it must be made sure
(e.g. by check with hand-held test instruments) each time before turning on the sensors and the
system that the environmental atmosphere to be monitored by the sensors is free of combustible
gases.