SUPREMA
264
SUPREMA Sensor Data Sheets
MSA
US
15.3 SUPREMA Sensor Data Sheet Fire Detector Apollo
Series 65 (not explosion-proof) External Power Supply
(without safety barrier)
Fig. 182
The cable screen is only connected to the SUPREMA.
*1 Apollo Fire Detector Series 65
Connect according to Apollo Mounting support 45681-200 Series 60/65 connection diagram
Max. 20 Fire Detector
*2 End of Line Resistor 2K2/0,5 W according to Apollo connection diagram 45681-200
Connection module: MFI (Fire Input Module)
Configuration: Internal power supply, without Zener barrier.
(Switch position S101: 1 + 2 = ON, 3 + 4 = OFF)
Adjust potentiometer P101 to left position
Connection
data:
Maximum nominal current 42 mA
Maximum nominal voltage 22 V
Power consumption 1.5 W (including cable length)
Cable type 2-core, 80 % screened
Maximum loop resistance 50 ohms (cable resistance)
Maximum cable length 2000 m (1.5 mm
2
cross section per wire)
Cross section per wire allowed 0.5 ... 2.5 mm
2

Table of Contents