Installation
SUPREMATouch
133
US
- Check the suitability of the installation site and the cabling requirements.
- Check the current and voltage supply and make sure it is suitable.
- Depending on the type of system shipped, install the switch cabinet, or the 19” mounting rack.
- Check the configuration of the modules and reconfigure if necessary.
- Install the modules in the 19” mounting rack (unless already installed at the factory).
- In the case of expanded systems with more than one 19” mounting rack, connect the CAN bus
or check the connection if it has already been made.
- Install the sensors and connect the wiring to the SUPREMA.
NOTE: Follow the installation instructions for hazardous areas!
- Connect the relay and current outputs to the external devices to be actuated.
- Connect the current and voltage supply.
After installation is complete, perform the start-up procedure as instructed in Chapter 11.
Unpacking
Perform the following steps on receipt of the shipment:
Installation Site
The SUPREMA control unit may be installed only outside of areas subject to the danger of explo-
sion. The specified temperature and humidity conditions must also be satisfied, and contact with
corrosive substances must be avoided.
NOTE: The SUPREMA installation site must be outside of hazardous area Zones 0,1 and 2 and
be free of combustible, explosive or corrosive gases.
Cabling
The terminal posts on the Analog Terminal Units (MAT module and MAT TS module) are de-
signed for the connection of conductors with a cross section in the range of 0.2 ... 1.5 mm
2
.
The terminal posts on the Relay Output Units (MRO 8, MRO 8 TS, and MRO 16 TS modules)
are designed for the connection of conductors with a cross section in the range of 0.2 ... 2.5 mm
2
.
The terminal posts on the External Connection Module MGT 40 TS are designed for the con-
nection of conductors with a cross section in the range of 0.2 ... 2.5 mm
2
.
On the Interconnection Board (MIB module), the terminal posts for the connection of the supply
voltages are designed for conductor cross sections of 0.2 ... 4.0 mm
2
, and the terminals for the
system failure relays are designed for conductor cross sections of 0.14 ... 1.5 mm
2
.
On the System Terminals Module (MST module), the terminals for Alarm Reset, Horn Reset, Re-
lay Inhibit, and Key Switch are designed for conductor cross sections in the range of
0.2 ... 2.5 mm
2
. The System Terminals Module (MST module) also has 2 SUB-D plug connector
strips (9-way) for the connection of the CAN bus and 3 SUB-D socket terminal strips for RS 232
connections.
Carefully unpack the device or its components, observing all of the instructions printed on or ac-
companying the packaging.
Also inspect the contents of the delivery to determine if any transport damage has occurred and
verify that everything listed in the shipping papers has in fact been received.