Installation
SUPREMATouch
135
US
Fig. 61 Allowed Conductor Cross Sections
Fig. 62 Cable Specifications
Module Conductor Cross Section
MAT/MAT TS Module 0.2 mm
2
- 1.5 mm
2
MRO 8/MRO 8 TS/MRO 16 TS Module 0.2 mm
2
- 2.5 mm
2
MRC TS Module (Supply Voltage, Relay Lock) 0.2 mm
2
- 2.5 mm
2
MGT 40 TS Module 0.2 mm
2
- 2.5 mm
2
MIB Module (Supply Voltage) 0.2 mm
2
- 4.0 mm
2
MIB Module (System Failure relays) 0.14 mm
2
- 1.5 mm
2
MSP Module (rack power supply, 150W) 0.2 mm
2
- 4.0 mm
2
MST Module (Alarm Reset, Horn Reset, Relay In-
hibit, Key Switch)
0.2 mm
2
- 2.5 mm
2
Type of
Sensor
Number of
Wires
Cable
Type
Max. cable
loop resist-
ance in ohms
Maximum
Length
Remarks
SafEye
FlameGard
4 x 1.5 mm
2
Y(C)Y 10 420 m Screened cable is
required
Ultima X
2 wire
2 x 0.5 mm
2
Y(C)Y 2000 m Screened cable is
required
Ultima X
3 wire
3 x 0.5 mm
2
3 x 1.0 mm
2
3 x 1.5 mm
2
Y(C)Y 300 m
750 m
1250 m
Screened cable is
required
PrimaX See transmitter
specific manual.
PrimaX IR See transmitter
specific manual.
FlameGard 5 MSIR 3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 1000 m See transmitter
specific manual.
FlameGard 5 UV/IR 3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 700 m See transmitter
specific manual.
FlameGard 5 UV/IR-
E
3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 700 m See transmitter
specific manual.
Ultima
MOS-5
3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 500 m See transmitter
specific manual.
Ultima
MOS-5E
3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 500 m See transmitter
specific manual.
Ultima
OPIR-5
3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 200 m Receiver w/o relay
and heater. See
transmitter specific
manual.
UltraSonic EX-5 3 x 1.5 mm
2
Y(C)Y 20 Ohm loop 1000 m See transmitter
specific manual.
UltraSonic IS-5 3 x 1.5 mm
2
Y(C)Y 40 Ohm loop 1800 m See transmitter
specific manual.