EasyManua.ls Logo

MSA SUPREMATouch - Page 184

MSA SUPREMATouch
309 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MSA AUER
MSA
Installation
SUPREMATouch
183
US
MAT Module/MAT TS Module/Sensor Connections
The function of the terminal connections of the MAT/MAT TS module depends on the module card
plugged into the rack.
Fig. 116 MAT/MAT TS Module, Terminal Assignment, Sensor Connections
Fig. 117 MAT Module/MAT TS Module, Connector Plug
For the 3-wire operation of the passive WT sensors, bridges are to be provided:
If wire jumpers cannot be installed at the terminals, they can be provided on the rear of the MAT
module in the form of solder bridges. (next to the ribbon plug of the MAT TS module).
(Chapter 10.3)
MGT 40 TS Module/Sensor Connections
Module Type Sensor
Type
Terminal 1 Terminal 2 Terminal 3 Terminal 4 Terminal 5
MAI Module with
MCI Module
active/
2-wire
4 ... 20 mA
signal (GND)
+24 V
MAI Module with
MCI Module
active/
3-wire
4 ... 20 mA
signal
+24 V GND
Terminal 1-2: BR K-K’
Terminal 4-5: BR D-D’
MAI Module with MCI
Module (WT)
MAI Module with MCI
Module (WT)
Measurem.
Point No.
MGT 40 TS Module
Terminal No.
active/
2-wire
active/
3-wire
1 2 signal signal
1 +24 V +24 V
4
3GND
6
2 5 signal signal
8 +24 V +24 V
7
10 GND
9

Table of Contents