SUPREMATouch
206
Installation
MSA
US
After adding the power consumption for the sensors, the following power values can be given for
the individual modules:
Fig. 148 Power Requirements of the System Modules
NOTE: The supply voltage may be turned on only after all required installation steps have been
completed and the installation has been verified during the startup procedure (Chapter 11).
Connection of the DC-Voltage Supply (MIB Module)
The system is supplied with 24 VDC (19.2 ... 32 VDC). There are 3 pairs of connection terminals
on the MIB module, so that the supply can originate from 3 different sources (redundancy). The
supplies are functionally equivalent, but the order in which the power is drawn is prioritised:
1
st
= EXT, 2
nd
= INT, 3
rd
= BAT. The changeover from one power source to another is accom-
plished on the system modules.
Type of Module Power (VA) Module
MCP module 5
MDO module 10
MDA module 1
MGO module 1
MAI module 1
MAO module 5
MRO 8 1,5
MRO 8 TS 1,5
MRO 16 TS 3
MBC module 2,5
CAUTION
The input voltage range (19.2 … 32 VDC) must not be exceeded! Higher voltage values can lead
to the destruction of the unit!