EasyManua.ls Logo

MSA SUPREMATouch - Page 249

MSA SUPREMATouch
309 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SUPREMA
248
Technical Data
MSA
US
MCI/MCI BFE Module: Current Input Unit
Order No.: 10043997 / 10044020
Function
- current/voltage source for active 4 ... 20 mA sensors (24 VDC)
- maximum current load for sensor supply 400 mA
- current limitation for sensor power supply (0.7 ... 2 A)
- voltage output short circuit-resistant
- current limitation for 4 ... 20 mA signal input (30 mA)
- multiplier resistor, 100 ohms (4 ... 20 mA = 0.4 ... 2.00 V)
- signal input options MCI: 4 ... 20 mA
Technical Data
MRO 10-8 Module: Relais Output Unit
Order No.: 10018946
Function
- relay module, installed on rear of rack
- 8 relays for common alarms, 1
st
-4
th
alarms, error, horn, inhibit, power
- actuated by the MGO module
- relays locked via the MST module (LOCR)
- switching status display (green LED, made = ON)
Technical Data
Operating voltage feed: 18.5 ... 32 VDC
Operating current: 1 mA
Current input (current limitation): 0 ... 30 mA
Contact input: 0 ... 27.5 V
Temperature range: 5 °C ... 55 °C
Humidity: 0 ... 90 % relative humidity noncondensing
Dimensions: 46 x 24 mm
Weight: 7 g
Relay operating voltage: 24 VDC
Relay operating current: 7 mA
Contact type: change-over contact
Contact load capacity: see relay contact data
Temperature range: 5 °C ... 55 °C
Humidity: 0 ... 90 % relative humidity noncondensing
Dimensions: 125 x 69 mm
Weight: 142 g

Table of Contents