SUPREMA
250
Technical Data
MSA
US
MRO 10-16-TS Module: Redundant Relais Output Unit (Rail-Mount Installation)
Order No.: 10021430
Function
- relay module, installed on mounting rail
- actuated by 2 MGO modules
- relays locked via the MRC module (LOCK)
- switching status display (green LED, made = ON)
- series connection of 2 contacts
- connection across 2 terminals
- contacts closed = status good
Technical Data
Relay Contact Data (MRO10)
Relay operating voltage: 19 ... 32 VDC
Relay operating current: 7 mA
Contact type: normally open
Contact load capacity: see relay contact data
Temperature range: 5 °C ... 55 °C
Humidity: 0 ... 90 % relative humidity noncondensing
Dimensions: 90 x 103 x 65 mm
Weight: 201 g
Maximum switching voltage: 250 VAC
250 VDC
Nominal current: 3 A
Maximum switching power:
- AC voltage 1500 VA
- DC voltage (from load limit curve) 24 VDC/3 A
50 VDC/0.3 A
100 VDC/0.1 A
Minimum switching power 6 VDC/1 A
12 VDC/100 mA
24 VDC/1 A