MIB Module: Interconnection Board
Order No.: 10032525
Function
- rack rear-panel wiring for 2 x MCP, 2 x MDA, 8 x MAI, 2 x MGO modules
- power supply for all modules (INT, EXT, BAT)
- connection for 3 x 24 VDC feed, screw terminals
- provides uninterruptible 24-V-system power
- data transfer between the modules over a CAN or SPI bus
- 2 system error relay, 1 change-over contact, 3 connecting terminals
- DIL switch for CAN rack ID, CAN bit rate, CAN bus terminating resistor
- 5 “dedicated” slots for 2 x MCP, 1 x reserved for MDC + MDO, 2 x MDA
- 8 undedicated slots for MAI, MGO, MAO modules etc.
- 2 undedicated slots for MAO, or MGO modules etc.
- electric connection for the inserted modules
- connection modules (MST, MUT etc.) are plugged into the rear of the MIB
Technical Data
Operating voltage feed: 19.2 ... 32 VDC
Maximum allowable operating current:
feed (+24 v): 20 A
(GND): 32 A
Feed connector cross section: 4 mm
2
, flexible
6 mm
2
, rigid
Power supply terminals: EXT, INT, BAT
Setting elements (rack no., CAN bit rate) 10-channel DIL switch
System error relay 3 A
Temperature range: 5 °C ... 55 °C
Humidity: 0 ... 90 % relative humidity noncondensing
Dimensions: 377 x 128 mm
Weight: 650 g