Maintenance and Service
SUPREMATouch
87
US
Examples
for MCI – Check 4 ... 20 mA
The sensor simulation module may be used only to the check and presetting and not to the cali-
bration.
for MPI – Check Catalytic Combustion Sensors
for MPI – Check Semiconductor Sensors
Sensor type: PrimaX
Measuring gas: Carbon monoxide
Zero gas: Air
Reference gas: Carbon monoxide
Ua at open switch [Normal operation]: 400 mV
Ua at closed switch [Alarm] : 1.9 V
Sensor type: Series 47k
Measuring gas: Methane
Zero gas: Air
Reference gas: Methane
Ux at open switch [Normal operation]: 0 mV
Ux at closed switch [Alarm] : 100 mV
Sensor type: DF-8101
Measuring gas: Acetone
Zero gas: Air
Reference gas: Acetone
Ux at open switch [Normal operation]: 1.6 V
Ux at closed switch [Alarm] : 1.1 V