3.3 Engine data 12, 16, 18 V 2000 B76 switchable 1800 rpm
Explanation:
DL Ref. value: Continuous power
BL Ref. value: Fuel stop power
A Design value
G Guaranteed value
R Guideline value
L Limit value up to which the engine can be operated without changes (e.g. to power settings).
N Value not yet defined
- Not applicable
X Applicable
Reference conditions
Engine model 12V2000B76
switchable
16V2000B76
switchable
18V2000B76
switchable
Application group 3B 3B 3B
Intake air temperature °C 25 25 25
Charge air coolant temperature °C - - -
Barometric pressure mbar 1000 1000 1000
Site altitude above sea level m 100 100 100
Table 33: Reference conditions
Power-related data (power ratings are net brake power as per ISO 3046)
Number of cylinders 12 16 18
Rated engine speed A rpm 1800 1800 1800
Continuous power ISO 3046 (10%
overload capability)
A kW 716 998 1097
Net brake power (without fan) (fuel
stop power ISO 3046)
A kW 789 1098 1207
Mean effective pressure (pme)
(continuous power ISO 3046)
bar 17.8 18.6 18.2
Mean effective pressure (pme)
(fuel stop power ISO 3046)
bar 19.6 20.5 20.0
Table 34: Power-related data (power ratings are net brake power as per ISO 3046)
Boundary conditions (for maximum power)
Number of cylinders 12 16 18
Intake depression (new filter) A mbar 15 15 15
Intake depression, max. L mbar 40 40 40
Exhaust overpressure A mbar 30 30 30
Exhaust overpressure, max. L mbar 50 50 50
30 | Technical Data | MS150118/00E 2014-07
TIM-ID: 0000054519 - 001

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MTU 12V2000B26F and is the answer not in the manual?

MTU 12V2000B26F Specifications

General IconGeneral
BrandMTU
Model12V2000B26F
CategoryEngine
LanguageEnglish

Related product manuals