Fault
code
Alarm text Meaning Task
079 L Bin-EXTERN 3 Alarm from external binary
channel 3
(Depending on the corresponding measur-
ing point, which is read via CAN bus)
080 L Bin-EXTERN 4 Alarm from external binary
channel 4
(Depending on the corresponding measur-
ing point, which is read via CAN bus)
089 ENGINE SPEED
LOW
Engine speed lower than 200
rpm;
automatic engine shutdown
Re-start the engine (→ Page 114).
090 IDLE SPEED LOW Idle speed not reached within a
specified period;
Termination of starting proce-
dure.
Note further alarms.
091 RUN UP SPEED
LOW
Run-up speed not reached
within a specified period;
Termination of starting proce-
dure.
Note further alarms.
092 START SPEED
LOW
Starter speed not reached with-
in a specified period;
Termination of starting proce-
dure.
Note further alarms.
093 PREHEAT TEMP.
LIMIT2
Coolant preheating tempera-
ture too low during starting
(2nd limit)
Termination of starting proce-
dure (depending on project de-
sign)
Check preheating pump / preheating sys-
tem (see manufacturer's documentation).
094 PREHEAT TEMP.
LIMIT1
Coolant preheating tempera-
ture too low during starting (1st
limit)
Check preheating pump / preheating sys-
tem (see manufacturer's documentation).
100 EDM NOT VALID Check sum error of measuring-
point data in EDM
If fault occurs repeatedly: Contact Service.
101 IDM NOT VALID Check sum error of measuring-
point data in IDM
If fault occurs repeatedly: Contact Service.
102 INVALID FUEL
CONS. 1
Check sum error of accumulat-
ed fuel consumption data in
EDM (redundant data record 1)
If fault occurs repeatedly: Contact Service.
103 INVALID FUEL
CONS. 2
Check sum error of accumulat-
ed fuel consumption data in
EDM (redundant data record 2)
If fault occurs repeatedly: Contact Service.
104 OP HOURS1 NOT
VALID
Check sum error of hour meter
data in EDM
If fault occurs repeatedly: Contact Service.
105 OP HOURS2 NOT
VALID
Check sum error of hour meter
data in IDM
If fault occurs repeatedly: Contact Service.
106 ERR REC1 NOT
VALID
Check sum error of fault mem-
ory in EDM (redundant data re-
cord 1)
If fault occurs repeatedly: Contact Service.
107 ERR REC2 NOT
VALID
Check sum error of fault mem-
ory in EDM (redundant data re-
cord 2)
If fault occurs repeatedly: Contact Service.