NIBE FIGHTER 1250
A
Heating settings
Quick guide – menu settings heat production
Operating mode
The menu can be accessed via the operating mode but-
ton. Here you select whether heat production is permit-
ted.
Menu 2.1 Curve coeffi cient [N]
The selected curve coeffi cient (heating curve) is shown
here. At value 0, the function “Own curve” is activated,
see menu 2.6.0.
The value can be set between curves 0 and 15.
- Factory setting: 9
Menu 2.2 Offset heating curve [N]
The selected heating curve offset is shown here.
Note! The value is changed using the “Heating curve
offset” knob.
The value can be set between -10 and +10.
- Factory setting: 0
Menu 2.3 Flow temp./Min [E]
The set minimum level for the supply temperature to the
heating system is shown here.
The calculated fl ow temperature never drops below the
set level irrespective of the outdoor temperature, curve
coeffi cient or offset heating curve.
The value is adjustable between 2 and 80 °C
- Factory setting: 15 °C
Menu 2.4 Flow temp./Max [E]
The set maximum level for the supply temperature to the
heating system is shown here.
The calculated supply temperature never exceeds the set
level irrespective of the outdoor temperature, curve coef-
fi cient or offset heating curve.
The value is adjustable between 10 and 80 °C
- Factory setting: 55 °C
Menu 1.0 is normally shown on the display
(the temperature in the hot water heater)
The plus and minus buttons and the enter
button can be used to scroll in the menu
system and change values in certain menus.
(See Front panel section)
Menu values