6. 0 Room temp./Settings
Menu 6.1 Room compensation [E]
A factor is selected here that determines how much the
fl ow temperature is affected by the difference between the
room temperature and the set room temperature. A higher
value gives a greater change.
The value can be set between 0.2 and 3.0.
- Factory setting: 1,0
Menu 6.2 Heating system [E]
You select here whether the room sensor should activate
heating system 1 (menu 2.0) or heating system 2 (menu
3.0).
Selection option From, System 1, System 2 or System 1+2.
- Factory setting: Off
Menu 6.3 Set room temp. [N]
Only shown when accessory RG05 is selected in menu
9.2.18.
The value is adjustable between 5 and 40 °C
- Factory setting: 20 °C
Menu 6.4 Room temp avg 1min [E]
Shows the average room temperature over the last minute.
Menu 6.5 Return [N]
Pressing the enter button returns you to Menu 6.0.
7.0 Clock
Menu 7.1 Date [N]
The current date is set here.
Menu 7.2 Time [N]
Here the current time is set.
Menu 7.3.0 Temp set back time 1 [E]
Settings, e.g. for night reduction can be selected in the
sub-menus to this menu.
Menu 7.3.1 Heating sys per. 1 [E]
Here you set which heating system is to be infl uenced by
day changes period 1. When heating system 2 is installed
both system 1 and/or 2 can be selected.
If room sensor is selected, the system choice is made in
menu 6.2.
Selection option From, System 1, System 2 or System 1+2
or Room sensor.
- Factory setting: Off
Menu 7.3.2 Set back temp. +/- [E]
Room temp change
Changes to the room temperature with a day change, e.g.
the night reduction is set here.
The value can be set between -10 and +10.
Factory setting: 0
Menu 7.3.3 – 7.3.9 Set time [E]
Monday – Sunday
The time for the day change, e.g. night reduction is chosen
here.
The value can be set between 00:00 and 23:45.
- Factory setting: 00:00-00:00
Menu 7.3.10 Return [E]
Pressing the enter button returns you to Menu 7.3.0
Menu 7.4.0 Temp set back time 2 [E]
Settings, e.g. for night reduction can be selected in the
sub-menus to this menu.
Menu 7.4.1 Heating sys per. 2 [E]
Here you set which heating system is to be infl uenced by
day changes period 2. When heating system 2 is installed
both system 1 and/or 2 can be selected.
If room sensor is selected, the system choice is made in
menu 6.2.
Selection option From, System 1, System 2 or System 1+2
or Room sensor.
- Factory setting: Off
Menu 7.4.2 Set back temp. +/- [E]
Room temp change
Changes to the room temperature with a day change, e.g.
the night reduction is set here.
The value can be set between -10 and +10.
Factory setting: 0
Control