38
NIBE FIGHTER 1250
D
Accessories
Room unit RE 10
Room unit RE 10 functions as an external
display with integrated room sensor for
FIGHTER 1250. The RE 10 can be used to read
and modify menus and values which are ac-
cessible in the heat pump. With the integra-
ted room sensor the calculated fl ow line is
corrected from the heat pump in a way that
means that the room temperature can be
held at a constant level in the room.
L
EK
Quick guidemenu settings
Room unit RE 10
Menu 8.1.1 Menu type [N]
The menu type is chosen here.
N] Normal, covers the normal user’s needs.
[E] Extended, shows all menus except the service menus.
[S] Service, shows all menus, returns to the previous
menu level 30 minutes after the last button was
pressed.
Selection option Normal, Extended or Service.
- Factory setting: Normal
Select “Service”.
Menu 9.2.6 Room disp Present [S]
Select “On” here whether the Room control unit is to
be activated or not.
Selection option Off and On.
- Factory setting: Off
Menu 9.2.18 Room sensor type [S]
Room sensor type is selected here. Menu 6.0 can be ac-
cessed.
Selection option From, RG05, RG10 or RE 10
- Factory setting: Off
Settings for desired room temperature etc can be selec-
ted in the sub-menus to 6.0.