NIBE FIGHTER 1250
Alarm indications
E
Alarm indications
In the event of an alarm, the background lighting in the
!
display and status lamp light red continually.
An alarm log is created with each alarm containing a !
number of temperatures, times and the status of out-
puts. The four most recent alarms are saved on menu
9.5.0 - 9.8.0.
Acknowledge alarm
Select ”On” in menu 9.10, or switch the power off and
then on to FIGHTER 1250 with switch (8).
If the alarm blocks hot water heating and it cannot be
acknowledged, you can gain access by selecting ”Winter
mode temp.”.
This is most easily carried out by holding the operating
mode button in for 7 seconds.
Alarm
no.
Alarm
text on
the dis-
play
Description May be due to
1 HP alarm The high pressure pressostat in Fighter 1250 has
tripped.
- No or low fl ow in the heating medium system.
- Closed valves to the radiators or under fl oor hea-
ting.
2 LP alarm The low pressure pressostat in Fighter 1250 has trip-
ped.
- Low fl ow in the brine system due to poor venting.
- Defective brine pump.
- Ice in evaporator due to low concentration of anti-
freeze.
- Leakage in the brine system.
4 TL alarm The temperature limiter in Fighter 1250 has tripped. - No fl ow through the immersion heater.
6 Low Brine
pump
alarm
Brine temperature is lower than that set in menu
5.11.8.
Automatic reset can be selected in menu 5.11.9
- Low fl ow in the brine system.
7 High VBF1 The alarm deploys when the fl ow sensor shows 90
ºC.
- No or low fl ow in the heating medium system.
10 High VVM The alarm deploys when jacket sensor in the hot
water heater shows 90 ºC.
11 High hot-
gas
The alarm deploys when the hot gas sensor shows
135 ºC.
3 alarms /4 hours permitted with automatic reset.
100-
116
Inverter er-
ror
- Property’s main fuse or heat pump group fuse has
blown.
Alarm that blocks the compressor (operating mode ”Winter mode temp.” without hot water connecting).
Alarm
no.
Alarm
text on
the dis-
play
Description May be due to
5 Ext KB
alarm
Deployed Brine pressostat/level monitor.
Alarm blocks compressor and operating mode
”Winter mode temp.” without hot water connec-
ting.
The alarm is activated in menu 9.2.11.
- Leakage in the brine system.
Alarms that can be selected via the display