Menu 9.12.6.0 Inv. templimit setup [S]
Shows the actual inverter temperature.
Settings regarding the temperature protection for the in-
verter can be made in the sub-menus to this menu.
Menu 9.12.6.1 Inv. templimit on [S]
Set the temperature at which frequency reduction should
come into force here.
The value is adjustable between 45 and 92 °C
- Factory setting: 87 °C
Menu 9.12.6.2 Inv. templimit diff [S]
Set how long during setting 9.12.6 that the frequency re-
duction should stop here.
The value is adjustable between 2 and 15 °C
- Factory setting: 5 °C
Menu 9.12.6.3 CompFreq dec/min [S]
How much the frequency is to be reduced each minute
when the temperature protection is active is set here .
The value is adjustable between 1 and 20 Hz
- Factory setting: 4 Hz
Menu 9.12.6.4 Return [S]
Pressing the enter button returns you to Menu 9.12.6.0.
Menu 9.12.7 Return [S]
Pressing the enter button returns you to Menu 9.12.0
Menu 9.13.0 System info [S]
The sub menus to this menu contain information that is
used when troubleshooting.
Menu 9.13.1 Com. Type Error [S]
Shows which unit that is not communicating with the CPU
card in the event of communication fault type 50.
Codes: 0x14 - ”RCU” 0xF1 - ”Buster card” 0xF5 - ”Relay
card” 0xF9 - ”Internal display” 0xFA - ”External display”.
Menu 9.13.2 CompReStartCounter [S]
Shows the number of compressor start attempts, resets at
normal compressor stop or alarm reset.
Menu 9.13.3 InvResetCounter [S]
Shows the number of reset attempts with command D01
of the inverter.
Menu 9.13.4 Inv. OnOffCounter [S]
Shows the number of reset attempts to start restart the
inverter by cutting the voltage with the contactor.
Menu 9.13.5 SW ver. PCB relay [S]
Shows the version number of the relay card 1.00 = 100.
Menu 9.13.6 SW ver. PCB 102 [S]
Shows the version number of the Buster card 1.00 = 100.
Menu 9.13.7 Return [S]
Pressing the enter button returns you to Menu 9.13.0
Menu 9.14 Return [S]
Pressing the enter button returns you to Menu 9.0.