65
NIBE FIGHTER 1250
Control
E
Menu 9.11.6 Time min freq heat [S]
Select here the time that the compressor is to run at fi xed
frequency after shifting to heating. The compressor then
runs at min frequency or at the frequency it had before hot
water/pool heating.
The value is adjustable between 3 and 60 minutes.
- Factory setting: 8 min
Menu 9.11.7 Max diff fl ow-cFlow [S]
Select here limitation of circ-pump fl ow when the degree
minute regulator is way off the set point. Max difference
between heating medium fl ow and calculated heating me-
dium fl ow.
The value is adjustable between 0.5 and 10.0 °C
- Factory setting: 1.0 °C.
Menu 9.11.8 Return [S]
Pressing the enter button returns you to Menu 9.11.0
Menu 9.12.0 Other inverter adj. [S]
Menu 9.12.1 Min CompFreq act/set [S]
Select here the min compressor frequency Display of the
actual and set via the display.
The value is adjustable between 30 and 120 Hz.
- Factory setting: 30 Hz
Menu 9.12.2 Max CompFreq act/set [S]
Select here the max limit for the compressor. Display of the
actual and set via the display.
The value is adjustable between 30 and 120 Hz.
- Factory setting: 120 Hz
Menu 9.12.3.0 CompFreq blockFreq [S]
In the sub menus to this menu, the frequency range that
the compressor is not permitted to work in set due to noise
and vibrations.
Menu 9.12.3.1 BlockFreq 1 from [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.2 BlockFreq 1 to [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.3 BlockFreq 2 from [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.4 BlockFreq 2 to [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.5 BlockFreq 3 from [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.6 BlockFreq 3 to [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.7 BlockFreq 4 from [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.8 BlockFreq 4 to [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.9 BlockFreq 5 from [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.10 BlockFreq 5 to [S]
Selection option From or between 30 and 120 Hz.
- Factory setting: Off
Menu 9.12.3.11 Return [S]
Pressing the enter button returns you to Menu 9.12.3.0
Menu 9.12.4 CompFreq powerguard [S]
Select here the frequency for the compressor when the
current limiter limits the compressor.
The value is adjustable between 45 and 120 Hz.
- Factory setting: 60 Hz
Menu 9.12.5.0 Inverter param rev [S]
Shows the actual version of the parameter list in the in-
verter.
Menu 9.12.5.1 Download inv para [S]
Selection option Off and On.
- Factory setting: Off
Menu 9.12.5.2 Return [S]
Pressing the enter button returns you to Menu 9.12.5.0

Table of Contents