64
NIBE FIGHTER 1250
Control
E
Menu 9.5.0 – 9.8.0 Log 1 – Log 4 [S]
The alarm logs are shown in the sub-menus of this menu.
Log 1 is the last alarm, log 2 the next last, etc.
Menu 9.x.1 Time [S]
Menu 9.x.2 Alarm number [S]
Alarm number Cause
1 HP alarm
2 LP alarm
4 TL alarm
5 Ext KB alarm
6 Low KB alarm
7 High VBF1
8 High VBR1
9 High KF
10 High VVM
11 High hotgas
20 Sensor fault VBF1
21 Sensor fault VBR1
22 Sensor fault VVM
23 Sensor fault VBF2
24 Sensor fault KF
25 Sensor fault KBin
26 Sensor fault KBout
27 Sensor fault HG
28 Sensor fault UG
100-116 Inverter error
Menu 9.x.3 Charging type [S]
Menu 9.x.4 Brine in [S]
Menu 9.x.5 Brine out [S]
Menu 9.x.6 Outdoor temp. [S]
Menu 9.x.7 Flow temp. [S]
Menu 9.x.8 Return temp. [S]
Menu 9.x.9 Hot water temp. [S]
Menu 9.x.10 Hot gas temp. [S]
Menu 9.x.11 Compr. time [S]
Menu 9.x.12 Electric b. time [S]
Menu 9.x.13 Circ-pump cont.sign [S]
Menu 9.x.14 Brine-pump cont.sign [S]
Menu 9.x.15 CompFreq cont.sign [S]
Menu 9.x.16 Relay 1-8 [S]
Menu 9.x.17 Relay 9-14 [S]
Menu 9.x.18 Inv. current (Apeak) [S]
Menu 9.x.19 Inv. VDC [S]
Menu 9.x.20 Inv. speed (RPM) [S]
Menu 9.x.21 Inv. error code [S]
Menu 9.x.22 Return [S]
Pressing the enter button returns you to Menu 9.x.0.
Menu 9.9 Reset log [S]
Select ”On” to erase the entire alarm log. The settings re-
turns to ”Off” once the action has been carried out.
Selection option Off and On.
- Factory setting: Off
Menu 9.10 Reset Alarm [S]
Select ”On” to reset/acknowledge alarms in FIGHTER 1250.
The setting returns to ”Off” when the action has been car-
ried out.
Selection option Off and On.
- Factory setting: Off
Menu 9.11.0 Add. heat settings [S]
Menu 9.11.1 CompFreq act/set [S]
Shown here are the set and actual set point frequencies to
the compressor after any blocks have occurred.
Setting the set point during manual control of the com-
pressor frequency.
The value is adjustable between 0 and 120 Hz.
Menu 9.11.2 Manual CompFreq [S]
Select ”On” to manually control the compressor frequency.
Selection option Off and On.
- Factory setting: Off
Menu 9.11.3 Max deltaF act/set [S]
The parameter for the heat regulator’s max change of the
set point is selected here. Display of the actual and set via
the display.
The value is adjustable between 1 and 10 Hz.
- Factory setting: 3 Hz
Menu 9.11.4 CompFreq regP [S]
Select P part for heat regulator.
The value can be set between 1 and 60.
- Factory setting: 5
Menu 9.11.5 Time min freq start [S]
Select here the time that the compressor during room
heating, is to run at min speed, after start.
The value is adjustable between 2 and 120 minutes.
- Factory setting: 70 min