NIBE FIGHTER 1250
4.0 Outdoor temperature
Menu 4.1 Outdoor av.temp 24h [E]
Shows the average outdoor temperature over the last 24
hours.
Menu 4.2 Outdoor av.temp 1m [E]
Shows the average outdoor temperature over the last
minute.
Menu 4.3 Return [E]
Pressing the enter button returns you to Menu 4.0.
5. 0 Brine in-/out- temp.
Menu 5.1 Status compressor [N]
Time to start
Shows the compressor status for the heat pump.
“Start in XX minutes”, means the compressor will start as
soon as the time condition permits.
“Compr. OFF” means that the compressor is not opera-
tional.
“Compr. ON” means that the compressor is operational.
Menu 5.2 Number of starts [N]
The accumulated number of starts with the compressor is
shown here.
Menu 5.3 Comp. acc. run time [N]
The accumulated time that the compressor has been in
operation is shown here.
Menu 5.4, Time between starts [E]
Time between compressor starts is set here.
The value is adjustable between 10 and 60 minutes.
- Factory setting: 20 min
Menu 5.5 Compr. starts at [E]
How low the degree-minutes may drop before the com-
pressor start can take place is set here.
The value can be set between -250 and -5.
- Factory setting: -60
Menu 5.6 Max returnt. act/set [E]
Shows the set max return temperature and calculated de-
pending on brine temperature.
The value is adjustable between 40 and 56 °C
- Factory setting: 53 °C
Menu 5.7 Hot gas temp. [E]
Shows the hot gas temperature.
Menu 5.8 Liquid line temp. [E]
Shows the liquid line temperature.
Menu 5.9 Bulb temperature [E]
Shows the bulb temperature.
Menu 5.10 Cond out temp./Max [E]
Shows the current and max temperature after the con-
denser. Max temperature drops automatically at low brine
temperature.
Menu 5.11.0 Brine diff set/pro [E]
Shows the actual and desired value for the brine’s tempera-
ture.
Menu 5.11.1 Brine-pump status [E]
Shows the brine pump’s status, On or Off .
Control
E