Wiring a Signaling Line Circuit (SLC)
,QVWDOODWLRQ
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-39
:LULQJD6LJQDOLQJ/LQH&LUFXLW6/&
2YHUYLHZRI6/&:LULQ
J
Communication between the control panel and intelligent and addressable initiating,
monitor, and control devices takes place through a Signaling Line Circuit (SLC). You
can wire an SLC loop to meet the requirements of NFPA Style 4, Style 6, or Style 7
circuits. This section covers the topics outlined in Table 2-15:
Table 2-15 SLC Wiring Topics
Topics Refer to...
Setting an Address for an MMX
or CMX Module
Figure 2-68 on page 2-49.
Methods for terminating wiring
leaving the control panel
"SLC Shield Termination" on page 2-42.
Wire Requirements for Two-Wire
SLC
"Wire Requirements for a Two-Wire SLC" on page 2-43, which
covers:
Loop resistance for a Two-Wire SLC.
Total wiring length for a Two-Wire SLC.
Typical Wiring for a Two-Wire SLC.
Wire Requirements for
Four-Wire SLC
"Wire Requirements for a Four-Wire SLC" on page 2-45, which
covers:
Loop resistance for a Four-wire SLC.
Total wiring length for a Four-wire SLC.
Typical Wiring for a Four-Wire SLC.
Wiring an ISO-X Isolator Module "Wiring an Isolator Module (ISO-X)" on page 2-48, which covers:
Description of an ISO-X Module.
Isolating a Branch of a Two-Wire SLC.
Wiring a Conventional Initiating
Device Circuit (IDC)
"Wiring an IDC with MMX Modules" on page 2-49, which covers:
Description of Monitor Modules (MMX-1, MMX-2, MMX-101).
Wiring a Two-Wire or Four-Wire IDC.
Wiring Notification Appliance
Circuits (NACs)
"SLC Wiring with CMX Modules" on page 2-55, which covers:
Description of Control Modules (CMX).
Wiring a CMX as Form-C Relay.
Wiring a Two-Wire (Style Y).
Wiring a four-wire NAC (Style Z).
Wiring an Intelligent Detector "SLC Wiring with an Intelligent Detector" on page 2-60, which
covers wiring a BX-101L in an SLC.
Wiring a BX-101L Addressable
Pull Station
"SLC Wiring with a BX-101L Addressable Manual Pull Station" on
page 2-61, which covers wiring an Intelligent Detector in an SLC.