EasyManuals Logo

Notifier ID50 User Manual

Notifier ID50
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
39 997-263, Issue 4
September 2002
5.5.3 Primary/Extend Delay Timers
The Primary Delay Timer allows an initial investigation time
of up to 300 seconds (default 30 seconds) to be entered or
changed. The Extend Delay Timer allows an additional delay
(default - 3 minutes) to be entered or changed. The total
delay time cannot exceed 10 minutes. To set delay times:
1 From the Commissioning menu, press the
1
button
on the numeric keypad to enter the Setup menu.
2 Press the
2
/
8
buttons to step through the Setup
menus to display the Primary Delay Time menu.
3 Press the
6
button. The display then prompts you
for the new value:
4 Enter the required delay time using the numeric
buttons; (e.g. to set the delay time to the maximum
value of 300seconds, first enter 3, then enter 0,0).
5 Press the
5
button to confirm and return to the
Setup menus.
6 Repeat steps 1 to 5 for the Extend Delay Time, using
the Extend Delay Time display and a maximum value
of 10minutes.
5.5.2 Date Format
This option is used to select one of three available date formats
for display on the LCD. The options available are dd/mm/yyyy,
mm/dd/yyyy or yyyy/mm/dd. To change the date format:
1 From the Commissioning menu, press the
1
button
on the numeric keypad to enter the Setup menu. The
LCD shows the Language menu.
Press the
2
/
8
buttons to scroll through the Setup
menu until the Date Format menu is displayed.
2 Press the 
6
 button to step through the alternative
Date Format settings.
3 Press 
4
 to return to the Commissioning menu.
[Setup] Date Format = mm/dd/yyyy
> : Change × : More < : Exit
[Setup] Language = English
> : Change × : More < : Exit
[Setup] Date Format = yyyy/mm/dd
> : Change × : More < : Exit
[Setup] Date Format = dd/mm/yyyy
> : Change × : More < : Exit
1
6
[Setup] Primary Delay Time = 30 Seconds
> : Change × : More < : Cancel
[Setup] Primary Delay Time = 30 Seconds
Enter new value ____ 3 : Confirm < : Cancel
[Setup] Primary Delay Time = 30 Seconds
Enter new value 300 3 : Confirm < : Cancel
1
6
or
82
5
[Setup] Language = English
> : Change × : More < : Exit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ID50 and is the answer not in the manual?

Notifier ID50 Specifications

General IconGeneral
BrandNotifier
ModelID50
CategoryFire Alarms
LanguageEnglish

Related product manuals