ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
54997-263, Issue 4
October 2002
5.6.1.2 Sensor Sensitivity Setting
This option allows the sensitivity of sensors to be changed
during device configuration. Access is via the Circuit
menu. Individual sensor Alarm and/or Day settings can
be changed.
Note: The ID60 Panel supports VIEW
TM
. The procedure
for changing this sensors sensitivity is different,
see Appendix 2, ID60 Single Loop Panel
Differences.
During configuration of the sensor sensitivity values, the
LCD returns to the previously configured value if any of
the following occurs:
a. The
4
button on the numeric keypad is pressed.
b. The panel state is unchanged for 1 minute.
c. A value outside the predefined operating limits (80%
to 120%) is entered.
To change the sensor sensitivity settings:
1 At the sensor attributes menu, press the
3
button
on the numeric keypad to display the Sensor Sensitivity
Setting menu:
2 Using the numeric keypad, press
1
to select the
Alarm Sensitivity setting or press
2
to select the
Day Mode Sensitivity setting.
3 At the appropriate prompt, use the numeric keypad to
enter the desired percentage value.
4 Press
5
to confirm the value entered or press
4
repeatedly to cancel the operation.
[Sensor nn - AAA] Sensitivity
Enter new alarm level : ____ < : Cancel
[Sensor nn - AAA] Sensitivity
1 : Alarm(100%) 2 : Day(100%) < : Cancel
[Sensor nn - AAA] Sensitivity
Enter day mode alarm : ____ < : Cancel
[Sensor nn - AAA] Sensitivity
1 : Alarm(120%) 2 : Day(80%) < : Cancel
or
21
1
2