EasyManuals Logo

Notifier ID50 User Manual

Notifier ID50
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
70997-263, Issue 4
October 2002
5.7.8 Zones
The Zones option determines the output response when
a zone detects an alarm. Each zone can be configured
as Yes (Y), No (N), Pulse (P), Coincidence (C) or Delay
(D) - see Section5.7 for definitions of these parameters.
If Day Mode is enabled (Section5.5.17, Day mode
activity) delays do NOT occur unless manually activated.
Manual activation can occur at any time of day - it does
not have to be during the set Day Mode period. Delays
are automatically de-activated with the end of the day
mode period.
To change the CBE Rules: Zone Setting from the CBE
Rules: Output menu, follow the described procedure
below:
1 From the menu options below, press the
9
button
to select the Zones option.
2 The LCD displays the pattern number and zone range
(either 1 to 16 for fire alarms or 17 to 32 for plant
alarms) on line 1. Line 2 of the LCD displays the
selected zones number, the full description of its
current status and the zones flashing editable status.
To select a zone, press the
6
button until the
appropriate zone number appears on line 2 in the
left-hand corner. The display cycles from 16 to 1 and
32 to 17.
3 To change a zones status, press the
2
/
8
buttons
until the required state is displayed.
4 Confirm the changes by pressing the
5
button.
Press
4
to cancel any changes.
CBE Rule:01 6:Class Change 7:Two Zone
9:Zones × : More
CBE Rule 01 Zones 1--------------------16
[Zone 01] [Yes ] YYYYNYYYNDDNCCNN
CBE Rule 01 Zones 1--------------------16
[Zone 06] [No ] YYYYNNYYNDDNCCNN
CBE Rule 01 Zones 1--------------------16
[Zone 06] [No ] YYYYNNYYNDDNCCNN
CBE Rule 01 Zones 1--------------------16
[Zone 06] [Yes ] YYYYNYYYNDDNCCNN
CBE Rule 01 Zones 1--------------------16
[Zone 06] [Pulse ] YYYYNPYYNDDNCCNN
6
2
8
x5
9

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ID50 and is the answer not in the manual?

Notifier ID50 Specifications

General IconGeneral
BrandNotifier
ModelID50
CategoryFire Alarms
LanguageEnglish

Related product manuals