10-3
10. Data Format Commands (P, G, R, W)
10.2 INPUT CONFIGURATION (“INP.CNFand “INPUt”)
TABLE 10.2 INPUT CONFIGURATION
BIT POSITION INP.CNF and INPUt
76543210
0 60 Line Frequency 60Hz
1 50 Line Frequency 50Hz
0 SLOW (14/SEC) Reading Rate
1 FAST (100/SEC) Reading Rate
0 UNIPOL Voltage Unipolar; tC
1 BIPOL Voltage Bipolar
00 C Unit of Temperature Degree C
01 F Unit of Temperature Degree F
10 k Unit of Temperature Degree K
1 1 (Not Used)
0 tC.CO.JC ENAbLE TC Cold Junction;
3.LINR 3 wire linear RTD;
NORMAL Bridge Limit; Process (Not Used)
1 tC.CO.JC dISABL TC Cold Junction;
4.LINR 4 wire linear RTD ;
SP1.L2.H SP1 lower overload limit and SP2
upper overload limit; Process - (Not Used)
0 IN.SC.OF dISABL Input Scale & Offset
1 IN.SC.OF ENAbLE Input Scale & Offset
0 RAtIO dISABL Strain Non-Ratiometric;
TC & Process Default
1 RAtIO ENAbLE Strain Ratiometric
EXAMPLE: To set the meter with line frequency of 50 Hz, slow reading rate (in case of
MENU 2), degree K unit of measure, TC Cold-Junction enabled (in case of TC mode)
and input scale and offset enabled:
The command data is 01010001BIN. = 51 HEX. Then send *W0A51

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega DP41-B Series and is the answer not in the manual?

Omega DP41-B Series Specifications

General IconGeneral
BrandOmega
ModelDP41-B Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals