10-12
10. Data Format Commands (P, G, R, W)
10.12 DATA FORMAT (“dAt.FMt”)
TABLE 10.12 DATA FORMAT
BIT POSITION DAt.FMt
76543210
0 Alarm Status - EXCLUDED
1 Alarm Status - INCLUDED
0 Peak / Valley Status - EXCLUDED
1 Peak / Valley Status - INCLUDED
0 Current Reading - EXCLUDED
1 Current Reading - INCLUDED
0 Filtered Value - EXCLUDED
1 Filtered Value - INCLUDED
0 Peak Value - EXCLUDED
1 Peak Value - INCLUDED
0 Valley Value - EXCLUDED
1 Valley Value - INCLUDED
0 Use Space as Separator
1 Use <CR. as Separator
0 Units of Measurement - EXCLUDED
1 Units of Measurement - INCLUDED
EXAMPLE: To format the data string, which includes Alarm status, Peak/Valley,
Current, Filtered input value status, units of measure and listed by underline instead of
space separated:
The command data is 11001111 BIN. = CF HEX. Then send *W1BCF