216
Comparison Instructions Section 3-6
S
1
through S
1
+2: Present Time Data
S
1
through S
1
+2 contain the present time data. S
1
through S
1
+2 must be in
the same data area.
Note When using the CPU Unit’s internal clock data for the comparison, set S
1
to
A351 to specify the CPU Unit’s internal clock data (A351 to A353).
S
2
through S
2
+2: Comparison Time Data
S
2
through S
2
+2 contain the comparison time data. S
2
through S
2
+2 must be
in the same data area.
15 8 07
S1
15 8 07
S1+1
15 8 07
S1+2
Seconds: 00 to 59 (BCD)
Minutes: 00 to 59 (BCD)
Hour: 00 to 23 (BCD)
Day: 01 to 31 (BCD)
Month: 01 to 12 (BCD)
Year: 00 to 99 (BCD)
15 8 07
S
2
15 8 07
S
2
+1
15 8 07
S
2
+2
Month: 01 to 12 (BCD)
Year: 00 to 99 (BCD)
Day: 01 to 31 (BCD)
Hour: 00 to 23 (BCD)
Minutes: 00 to 59 (BCD)
Seconds: 00 to 59 (BCD)

Table of Contents