726
High-speed Counter/Pulse Output Instructions Section 3-20
Independent Mode Positioning
When independent mode operation is started, pulse output will be continued
until the specified number of pulses has been output.
Note (1) Pulse output will stop immediately if the CPU Unit is changed to PRO-
GRAM mode.
(2) The number of output pulses must be set each time output is restarted.
(3) The number of output pulses must be set in advance with PULS(881).
Pulses will not be output for SPED(885) if PULS(881) is not executed first.
Stopping
pulse out-
put
Stop
pulse
output
Immediate
stop
Stops the pulse
output immedi-
ately.
SPED(885)
(Continuous)
INI(880)
Stop
pulse
output
Immediate
stop
Stops the pulse
output immedi-
ately.
SPED(885)
(Continuous)
SPED(885)
(Continuous, Tar-
get frequency of
0 Hz)
Operation Purpose Application Frequency changes Description Procedure/
instruction
Pulse frequency
Present frequency
Execution of INI
(
880
)
Time
Pulse frequency
Present frequency
Execution of SPED
(
885
)
Time