Clock Instructions Section 3-26
Examples When CIO 0.00 turns ON in the following example, the seconds data in D100
and D101 (123,456 seconds) is converted to hours/minutes/seconds data and
the result is output to D200 and D201.
3-26-5 CLOCK ADJUSTMENT: DATE(735)
Purpose Changes the internal clock setting to the setting in the specified source words.
Note The internal clock setting can also be changed from the CX-Programmer or
the CLOCK WRITE FINS command (0702).
Ladder Symbol
Variations
Applicable Program Areas
0.00
D100
D200
S: D100
D101
D: D200
D201
123,456 seconds
Hours/minutes/secondsSeconds
17 minutes, 36 seconds
34 hours
S
DATE(735)
S: First source word
Variations Executed Each Cycle for ON Condition DATE(735)
Executed Once for Upward Differentiation @DATE(735)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification Not supported.
Block program areas Step program areas Subroutines Interrupt tasks
OK OK OK OK