64
Using Tasks Section 2-2
Task Number when
Program Stopped (A294)
The type of task and the current task number when a task stops execution
due to a program error will be stored as follows:
This information makes it easier to determine where the fatal error occurred,
and it will be cleared when the fatal error is cleared. The program address
where task operation stopped is stored in A298 (rightmost bits of the program
address) and in A299 (leftmost bits of the program address).
Type A294
Cyclic task 0000 to 001F hex (correspond to task numbers 0 to 31)
Interrupt task 8000 to 80FF hex (correspond to interrupt task numbers 0 to 255)