Digital Operation Display Functions and Levels
5-5
Quick Programming Parameters that are Available with Enabled PI Controller
Following list shows the parameters that are available additionally in Quick Programming Mode whenever the
PI controller is enabled. The default settings are also set automatically to settings commonly used with the PI
controller.
E1-01
Input voltage
setting
Sets the inverter input voltage. This set
value will be the basis for the protection
functions.
155 to
255
*1
200 V
*1
No Q 300H
E2-01
Motor rated cur-
rent
Sets the motor rated current in Amps.
This set value becomes the base value for
motor protection and torque limit. It is an
input data for autotuning.
0.32 to
6.40
*2
1.90 A
*3
No Q 30EH
*1. These are values for a 200 V class Inverter. For 400 V class Inverters the value has to be doubled.
*2. The setting range is from 10% to 200% of the Inverter rated output current.
*3. The factory setting depends on the Inverter capacity (the value for a 200 V Class Inverter for 0.4 kW is given).
Parame-
ter Num-
ber
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
H3-08
Analog input
A2 signal level
selection
Selects the signal level input at multi-
function analog input A2.
0: 0 to +10V (11 bit input)
2: 4 to 20mA (9 bit input)
3: 0 to 20mA (9 bit input)
0, 2, 3 2 No
Q
*1
*1. Parameter is only moved into Quick Programming Mode when PI controller is enabled, otherwise the parameter is only available in Advanced
Programming Mode.
417H
H3-09
Analog input
A2 function
selection
Selects the multi-function analog input
function for terminal A2. Refer to the
table
H3-09 Settings for the explanation
of the settings range.
0 to 1F
B
*2
*2. Setting switched to “B” (PI feedback) only when PI controller is enabled, otherwise default setting is “2” (Auxiliary Reference)
No
Q
*1
418H
H3-13
Terminal A1/
A2 switching
Selects on which terminal the main fre-
quency reference can be input.
0: Use analog input 1 on terminal A1 for
main frequency reference.
1: Use analog input 2 on terminal A2 for
main frequency reference.
0, 1 0 No
Q
*1
41CH
b5-31 PI unit selection
Selects the units for the PI controller val-
ues (b5-19, U1-24, U1-38).
Refer to table
b5-31 Settings for the
explanation of the setting range
0 to 11 0 No
Q
*1
1EDH
b5-02
Proportional (P)
gain
Sets the proportional gain of the PI con-
troller. P control is not performed when
set to 0.00
0.00 to
25.00
1.00 Yes
Q
*1
1A6H
b5-03 Integral (I) time
Sets the integral time of the PI controller.
I control is not performed when set to 0.0.
0.0 to
360.0
1.0 sec. Yes
Q
*1
1A7H
Parame-
ter Num-
ber
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Varispeed E7 and is the answer not in the manual?

Omron Varispeed E7 Specifications

General IconGeneral
BrandOmron
ModelVarispeed E7
CategoryInverter
LanguageEnglish

Related product manuals