5-8
îš‹ Application Parameters: b
Operation Mode Selections: b1
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
b1-01
Reference source
selection
Sets the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (ana-
log inputs)
2: Serial communications (RS
422/485)
3: Option Card (connected on
CN2)
0 to 3 1 No Q 180H
6-5
6-52
b1-02
RUN command
source selection
Sets the run command input
method.
0: Digital Operator
1: Control circuit terminal (digital
multifunction inputs)
2: Serial communications (RS
422/485)
3: Option Card (connceted on
CN2)
0 to 3 1 No Q 181H
6-9
6-52
b1-03
Stopping method
selection
Selects the stopping method when
the Run signal is removed
0:Deceleration to stop
1:Coast to stop
2:DC injection to stop
3:Coast to stop with timer (New
Run commands are disregarded
while coasting.)
0 to 3 0 No Q 182H 6-11
b1-04
Prohibition of
reverse operation
0:Reverse enabled
1:Reverse disabled
2: Output Phase Rotation (both
rotational directions are
enabled)
3: Output Phase Rotation with
Reverse disabled.
0 to 3 0 No A 183H 6-37
b1-07
Operation selec-
tion after switch-
ing to remote
mode
Selects if the Inverter accepts a
Run command that is already set
when the Inverter is switched to
Remote Mode.
0:Preset Run signals are disre-
garded.
(Run signal has to be cycled
once to become active)
1:Preset Run signals become
effective immediately after
switching to the Remote mode.
0 or 1 0 No A 186H –
b1-08
Run command
selection in pro-
gramming modes
Selects if a Run signal will be
accepted when the Inverter is in
any Programming Mode.
0:Run signal is disregarded.
1:Run signal is accepted (Dis-
abled for b1-02 = 0).
0 or 1 0 No A 187H –