5-40
Motor Autotuning: T
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
T1-02
Motor output
power
Set the output power of the motor
in Kilowatts.
0.00 to
650.00
0.40
kW
*1
*1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
No A 702H 4-7
T1-04
Motor rated cur-
rent
Set the rated current of the motor in
Amps.
0.32 to
6.40
*2
*2. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
1.90 A
*1
No A 704H 4-7