User Parameter Tables
5-39
Copy Function: o3
o2-10
Fan operation
time setting
Sets the initial value of the fan
operation time.
The fan operation time is accumu-
lated from the set value.
0 to
65535
0 hr. No A 50EH 6-112
o2-12
Fault trace initial-
ize
0: No change
1: Initialized. After setting ”1“ o2-
12 will return to ”0“
0 or 1 0 No A 511H 6-112
o2-14
kWh monitor ini-
tialize
Resets the monitor parameters
U1-29 and U1-30 back to zero.
0: No change
1: Reset to zero
0 or 1 0 No A 512H 6-112
o2-15
HAND Key func-
tion selection
*3
If set to 0 the HAND key on the
HOA Digital Operator is disabled
and the Inverter will not enter the
HAND mode and start to run when
the HAND key is pressed.
0: HAND key disabled
1: HAND key enabled
0 or 1 0 No A 513H 6-113
o2-17
Standard / IP54
Selection
Selects whether the Inverter is in
standard (IP00 or NEMA 1 / IP20)
or IP54 protection class.
0: IP00 or NEMA 1 / IP20
1: IP54
0 or 1
*4
No
*5
51BH 6-113
*1. This parameter is effective only when the LED or LCD Digital Operator is used.
*2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
*3. This parameter is effective only when the HOA operator JVOP-162 is used.
*4. Factory setting depends on the protection class of the Inverter.
*5. The access level depends on the setting of o2-09: When o2-09 is set to “2” or “5” parameter o2-17 is accessable.
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
o3-01
Copy function
selection
0: Normal operation
1: READ (Inverter to Operator)
2: COPY (Operator to Inverter)
3: Verify (compare)
0 to 3 0 No A 515H 6-113
o3-02
Read permission
selection
0: READ prohibited
1: READ permitted
0 or 1 0 No A 516H 6-113
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page

Table of Contents