5-38
Multi-function Selections: o2
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
o2-01
LOCAL/
REMOTE key
enable/disable
*1
Enables/disables the LOCAL/
REMOTE key
0:Disabled
1:Enabled (Switches between the
Digital Operator and the param-
eter settings b1-01, b1-02.)
0 or 1 1 No A 505H 6-112
o2-02
STOP key during
control circuit
terminal opera-
tion
*1
Enables/disables the STOP key
0:Disabled (When the run com-
mand is issued from an external
terminal, the Stop key is dis-
abled.)
1:Enabled (Effective even during
run.)
0 or 1 1 No A 506H 6-112
o2-03
User parameter
initial value
Clears or stores user initial values.
0:Stored/not set
1:Begins storing
(Records the set parameters as
user initial values.)
2:Clearing memory (Clears all
recorded user initial values)
When the set parameters are
recorded as user initial values,
1110 can be set in A1-03 to recall
them.
0 to 2 0 No A 507H 6-112
o2-04 kVA selection
Do not set unless after replacing
the control board. (Refer to
page 5-
47
for the setting values)
0 to FF
0
*2
No A 508H 5-47
o2-05
Frequency refer-
ence setting
method selection
When the frequency reference is
set on the Digital Operator fre-
quency reference monitor, sets
whether the Enter key is necessary
or not.
0:Enter key needed
1:Enter key not needed
0 or 1 0 No A 509H 6-112
o2-06
Operation selec-
tion when digital
operator is dis-
connected
Sets the operation when the Digital
Operator is disconnected.
0:Disabled (Operation continues
even if the Digital Operator is
disconnected.)
1:Enabled (OPR is detected at
Digital Operator disconnection.
Inverter output is switched off,
and fault relay is operated.)
0 or 1 0 No A 50AH 6-112
o2-07
Cumulative oper-
ation time setting
Sets the cumulative operation time.
The operation time is accumulated
form the set value.
0 to
65535
0 hrs No A 50BH 6-112
o2-08
Cumulative oper-
ation time selec-
tion
0:Accumulated Inverter power on
time
1:Accumulated Inverter run time.
0 or 1 1 No A 50CH 6-112
o2-09 Initialize Mode
2: Europe Spec.
5: PV-E Spec.
6: Chinese Spec.
2, 5, 6 2 No A 50DH -