5-14
Energy Saving: b8
8 Bar: Bar Bar
9 Pa: Pascal Pa
10 C: Degree Celsius C
11 Mtr: Meters Mtr
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
b8-01
Energy-saving
mode selection
Enables or disables the energy-sav-
ing function.
0: Disable
1: Enable
0 or 1 0 No A 1CCH 6-98
b8-04
Energy-saving
coefficient
Sets the energy-saving coefficient.
Adjust the value in 5% steps until
the output power becomes mini-
mal.
0.0 to
655.00
*1
*1. The factory setting depends on the Inverter capacity.
No A 1CFH 6-98
b8-05
Power detection
filter time con-
stant
Sets the time constant for output
power detection.
0 to
2000
20msec No A 1D0H 6-98
b8-06
Search operation
voltage limiter
Sets the limit value of the voltage
control range during search opera-
tion.
Set to 0 to disable the search oper-
ation. 100% is the motor rated volt-
age.
0 to
100
0% No A 1D1H 6-98
Setting
Value
Function Displayed Unit

Table of Contents