EasyManuals Logo

Omron Varispeed E7 User Manual

Omron Varispeed E7
321 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
5-14
Energy Saving: b8
8 Bar: Bar Bar
9 Pa: Pascal Pa
10 C: Degree Celsius C
11 Mtr: Meters Mtr
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
b8-01
Energy-saving
mode selection
Enables or disables the energy-sav-
ing function.
0: Disable
1: Enable
0 or 1 0 No A 1CCH 6-98
b8-04
Energy-saving
coefficient
Sets the energy-saving coefficient.
Adjust the value in 5% steps until
the output power becomes mini-
mal.
0.0 to
655.00
*1
*1. The factory setting depends on the Inverter capacity.
No A 1CFH 6-98
b8-05
Power detection
filter time con-
stant
Sets the time constant for output
power detection.
0 to
2000
20msec No A 1D0H 6-98
b8-06
Search operation
voltage limiter
Sets the limit value of the voltage
control range during search opera-
tion.
Set to 0 to disable the search oper-
ation. 100% is the motor rated volt-
age.
0 to
100
0% No A 1D1H 6-98
Setting
Value
Function Displayed Unit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Varispeed E7 and is the answer not in the manual?

Omron Varispeed E7 Specifications

General IconGeneral
BrandOmron
ModelVarispeed E7
CategoryInverter
LanguageEnglish

Related product manuals