EasyManuals Logo

Omron Varispeed E7 User Manual

Omron Varispeed E7
321 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
User Parameter Tables
5-17
Carrier Frequency: C6
Param-
eter
Num-
ber
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
C6-01
Normal duty
selection
1: Normal Duty 1
2: Normal Duty 2
1 or 2 1 No A 223H 6-2
C6-02
Carrier fre-
quency selection
Selects the carrier frequency.
Select F to enable detailed settings
using parameters C6-03 to C6-05.
0 to F
6
*1
*1. The factory setting depends on the Inverter capacity and the protection class.
No A 224H
4-11
6-2
C6-03
Carrier fre-
quency upper
limit
Sets the carrier frequency upper limit
and lower limit in kHz units.
The carrier frequency gain is set as fol-
lows:
K is a coefficient that depends on the
setting of C6-03.
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
2.0 to
15.0
*2
*3
*2. The setting range depends on the Inverter capacity.
*3. This parameter can only be set when C6-02 is set to F.
15.0
kHz
*1
No A 225H 6-2
C6-04
Carrier fre-
quency lower
limit
0.4 to
15.0
*2
*3
15.0
kHz
*1
No A 226H 6-2
C6-05
Carrier fre-
quency propor-
tional gain
00 to
99
*3
00 No A 227H 6-2
Carrier frequency
Output frequency x (C6-05) x K
(Max. output frequency)
Output fre
-
quency

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Varispeed E7 and is the answer not in the manual?

Omron Varispeed E7 Specifications

General IconGeneral
BrandOmron
ModelVarispeed E7
CategoryInverter
LanguageEnglish

Related product manuals