User Parameter Tables
5-21
Motor Setup: E2
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
E2-01
Motor rated cur-
rent
Sets the motor rated current.
This set value will become the ref-
erence value for motor protection
and torque limits.
This parameter is an input data for
autotuning.
0.32 to
6.40
*1
*1. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
1.90 A
*2
*2. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given
No Q 30EH
6-33
6-99
E2-03
Motor no-load
current
Sets the motor no-load current.
This parameter is automatically set
during autotuning.
0.00 to
1.89
*3
*3. The setting range is 0.00 A to (E2-01 - 0.01 A).
1.2 A
*2
No A 310H 6-99
E2-05
Motor line-to-line
resistance
Sets the motor phase-to-phase
resistance in Ω units.
This parameter is automatically set
during autotuning.
0.000
to
65.000
9.842
Ω
*2
No A 312H 6-99