User Parameter Tables
5-33
Load Detection: L6
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
L6-01
Load detection
selection
0: Load detection disabled.
1: Overload detection only at
speed agree; operation contin-
ues (alarm).
2: Overload detection continu-
ously during operation; opera-
tion continues (alarm).
3: Overload detection only at
speed agree; coast to stop
(fault).
4: Overload detection continu-
ously during operation; coast to
stop (fault).
5: Loss of load detection only at
speed agree; operation contin-
ues (alarm).
6: Loss of load detection continu-
ously during operation; opera-
tion continues (alarm).
7: Loss of Load detection only at
speed agree; coast to stop
(fault).
8: Loss of Load detection continu-
ously during operation; coast to
stop (fault).
0 to 8 6 No A 4A1H 6-30
L6-02
Load detection
level
Inverter rated current is set as
100%.
0 to
300
15% No A 4A2H 6-30
L6-03
Load detection
time
Sets the overload/loss of load
detection time.
0.0 to
10.0
10.0
sec.
No A 4A3H 6-30