6-20
Setting Precautions
The stall prevention level during deceleration differs depending on the inverter rated voltage and input
voltage. Refer to the following table for details.
When using a braking option, be sure to set parameter L3-04 to 0.
Inverter Rated/Input Voltage Stall Prevention Level during Deceleration
200 V class 380 VDC
400 V class
E1-01 400 V 760 VDC
E1-01 < 400 V 660 VDC