Output Terminal Functions
6-65
Zero Speed (Setting: 1)
Fig 6.48 Timing Chart for Zero-speed
Inverter Operation Ready (Setting: 6)
If a multi-function digital output is programmed to 6 the output will be switched ON when the initialisation of
the Inverter at startup has finished without any faults.
During DC Bus Undervoltage (Setting: 7)
If a multi-function digital output is programmed to 7 the output is switched ON as long as a DC bus undervolt-
age is detected.
During Baseblock (Setting: 8)
If a multi-function digital output is programmed to 8 the output is switched ON as long as the Inverter output
is base blocked.
Frequency Reference Source Selection (Setting: 9)
If a multi-function digital output is programmed to 9 the output is ON when the Digital Operator is selected as
frequency reference source. If any other frequency reference is selected the output is switched OFF.
Run Command Source Selection Status (Setting: A)
If a multi-function digital output is programmed to A the output is switched ON when the digital operator is
selected as RUN command source. If any other RUN command source is selected output is switched OFF.
Fault (Setting: E)
If a multi-function digital output is programmed to E the output is switched ON when any fault different from
CPF00 and CPF01 occurs. The output is also not switched in alarm condition. (Refer to Chapter 7, Trouble-
shooting for fault and alarm lists.)
Minor Fault (Alarm) (Setting: 10)
If a multi-function digital output is programmed to 10 the output is switched ON when the Inverter is in alarm
condition (refer to page 7-8, Alarm Detection pp.).
OFF
The output frequency is higher than the zero speed level (DC injection braking start level,
b2-01).
ON
The output frequency is lower than the zero speed level (DC injection braking start level,
b2-01).
Zero speed level (b2-01)
OFF
ON
Zero-speed output
Output frequency