7-12
PI Control Setup Error
The following settings have been
made at the same time.
b5-01 (PI Control Mode Selection)
has been set to a value different
from 0.
b5-15 (PI Sleep Function Opera-
tion Level) has been set to a value
different from 0.
b1-03 (Stopping Method Selection)
has been set to 2 or 3.
Check the settings of
parameters b5-01, b5-15
and b1-03
OPE09
PI Selection
V/f Parameter Setting Error
Parameters E1-04, E1-06, E1-07, E1-
09 and E1-11 do not satisfy the fol-
lowing conditions:
E1-04 (FMAX) E1-11 (FMID2)
> E1-06 (FA) > E1-07 (FB) E1-
09 (FMIN)
Check the parameter
settings of E1-
A frequency/voltage
value might be set
higher than the maxi-
mum frequency/volt-
age.
OPE10
V/f Ptrn Setting
Carrier Frequency Parameter Set-
ting Error
One of the following parameter set-
ting errors exists:
Carrier frequency Gain C6-05 > 6
and C6-03 (Carrier Frequency
Upper Limit) < C6-04 (Carrier Fre-
quency Lower Limit)
Upper/lower limit error in C6-03
and C6-04.
Check the parameter set-
tings of C6-02 to C6-05.
OPE11
CarrFrq/On-Delay
EEPROM write error
The NV-RAM data do not match
the EEPROM data
A verification error occurred when
writing EEPROM.
Cycle the Inverter
power supply.
Try to initialize the
Inverter.
ERR
EEPROM R/W Err
Table 7.3 Operator Programming Errors