EasyManuals Logo

Omron Varispeed E7 User Manual

Omron Varispeed E7
321 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #289 background imageLoading...
Page #289 background image
7-14
Copy
The Inverter type or software number was
different from the stored data in the digi-
tal operator
Use stored data of the same product (E7)
and software number (U1-14) only.
CPE
ID UNMATCHED
The capacity of the Inverter and the
capacity of the stored data in the Digital
Operator are different.
Use stored data for the same Inverter
capacity only (o2-04).
VA E
INV. KVA UNMATCH
A parameter setting written to the
Inverter was different from the setting
stored in the Digital Operator.
Retry the COPY function (o3-01 = 2)
CYE
COPY ERROR
Upon completion of the COPY function,
the Inverter’s data checksum was differ-
ent than the digital operator’s data check-
sum.
Retry the COPY function (o3-01 = 2)
CSE
SUM CHECK ERROR
Verify
The set value of the digital operator and
the Inverter do not match
Retry the VERIFY function (o3-01 = 3)
VYE
VERIFY ERROR
Table 7.5 Digital Operator Copy Function Faults