2-8
The wire thickness is set for copper wires at 75°C.The wire thickness is set for copper wires at 75°
E7Z2037
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M10 17.6 to 22.5
70 to 95
(2/0 to 4/0)
70
(2/0)
Power cables,
e.g., 600 V vinyl
power cables
3
M8 8.8 to 10.8
6 to 16
(10 to 4)
–
M10 17.6 to 22.5
35 to 70
(2 to 2/0)
35
(2)
r/l1, Δ/l2 M4 1.3 to 1.4
0.5 to 4
(20 to 10)
1.5
(16)
E7Z2045
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M10 17.6 to 22.5
95
(3/0 to 4/0)
95
(3/0)
3
M8 8.8 to 10.8
6 to 16
(10 to 4)
–
M10 17.6 to 22.5
50 to 70
(1 to 2/0)
50
(1)
r/l1,
Δ/l2 M4 1.3 to 1.4
0.5 to 4
(20 to 10)
1.5
(16)
E7Z2055
R/L1, S/L2, T/L3, , 1
M12 31.4 to 39.2
50 to 95
(1/0 to 4/0)
50 × 2P
(1/0 × 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M10 17.6 to 22.5
90
(4/0)
90
(4/0)
3
M8 8.8 to 10.8
6 to 70
(10 to 2/0)
–
M10 17.6 to 22.5
35 to 95
(3 to 4/0)
50
(1/0)
r/l1,
Δ/l2 M4 1.3 to 1.4
0.5 to 4
(20 to 10)
1.5
(16)
E7Z2075
R/L1, S/L2, T/L3, , 1
M12 31.4 to 39.2
95 to 122
(3/0 to 250)
95 × 2P
(3/0 × 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M10 17.6 to 22.5
95
(3/0 to 4/0)
95 × 2P
(3/0 × 2P)
3
M8 8.8 to 10.8
6 to 70
(10 to 2/0)
–
M10 17.6 to 22.5
95 to 185
(3/0 to 400)
95
(3/0)
r/l1,
Δ/l2 M4 1.3 to 1.4
0.5 to 4
(20 to 10)
1.5
(16)
E7Z2090
R/L1, S/L2, T/L3, , 1
M12 31.4 to 39.2
150 to 185
(250 to 400)
150 × 2P
(250 × 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
95 to 150
(4/0 to 300)
95 × 2P
(4/0 × 2P)
3
M8 8.8 to 10.8
6 to 70
(10 to 2/0)
–
M12 31.4 to 39.2
70 to 150
(2/0 to 300)
70 × 2P
(2/0 × 2P)
r/l1,
Δ/l2 M4 1.3 to 1.4
0.5 to 4
(20 to 10)
1.5
(16)
E7Z2110
R/L1, S/L2, T/L3, , 1
M12 31.4 to 39.2
240 to 300
(350 to 600)
240 × 2P, or
50 × 4P
(350 × 2P, or
1/0 × 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
150 to 300
(300 to 600)
150 × 2P, or
50 × 4P
(300 × 2P, or
1/0 × 4P)
3
M8 8.8 to 10.8
6 to 70
(10 to 2/0)
–
M12 31.4 to 39.2
150
(300)
150 × 2P
(300 × 2P)
r/l1,
Δ/l2 M4 1.3 to 1.4
0.5 to 4
(20 to 10)
1.5
(16)
Table 2.1 200 V Class Wire Sizes
Inverter
Model
CIMR-
Terminal Symbol
Termi-
nal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes
mm
2
(AWG)
Recom-
mended
Wire Size
mm
2
(AWG)
Wire Type

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Varispeed E7 and is the answer not in the manual?

Omron Varispeed E7 Specifications

General IconGeneral
BrandOmron
ModelVarispeed E7
CategoryInverter
LanguageEnglish

Related product manuals